Heat Resistant Electrical Insulating Double Sided Paper Crepe Insulation Crepe Paper for Transformer

Product Details
Customization: Available
Material: Wood Pulp
Tensile Strength: 28-78min
Gold Member Since 2023

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

to see all verified strength labels (11)
  • Heat Resistant Electrical Insulating Double Sided Paper Crepe Insulation Crepe Paper for Transformer
  • Heat Resistant Electrical Insulating Double Sided Paper Crepe Insulation Crepe Paper for Transformer
  • Heat Resistant Electrical Insulating Double Sided Paper Crepe Insulation Crepe Paper for Transformer
  • Heat Resistant Electrical Insulating Double Sided Paper Crepe Insulation Crepe Paper for Transformer
  • Heat Resistant Electrical Insulating Double Sided Paper Crepe Insulation Crepe Paper for Transformer
  • Heat Resistant Electrical Insulating Double Sided Paper Crepe Insulation Crepe Paper for Transformer
Find Similar Products

Basic Info.

Model NO.
crepe paper
Wide Usage
Oil-Immersed Transformer
pH of Aqueous Extract
6-8
Rated Voltage
35kv
Type
Insulation Paper
Product Name
Best Quality Crepe Paper
OEM,ODM Service
Avaliable
Application
High Temperature
Elongation
15% - 300%
Transport Package
Rolling up by Pallet or Carton
Trademark
powerwell
Origin
Hunan, China
Production Capacity
500 Ton/Tons Per Month

Product Description

Heat Resistant Electrical Insulating Double Sided Paper Crepe Insulation Crepe Paper for Transformer

Heat Resistant Electrical Insulating Double Sided Paper Crepe Insulation Crepe Paper for Transformer

Typical properties of Insulation Crepe Paper

Properties

Units

SPECIFIED VALUES
Under IEC-60554-3-3

TYPICAL OBTAINED TEST VALUES, RBL(GSM)

60/120

60/150

100/200

100/250

Thickness Tolerance

Mm

 

0.33

0.39

0.48

0.55

Hill Count

Counts/
10 mm

 

11

16

11

16

Extended Tensile Index(MD)

Nm/g Min

39

64  

66

65

68

Elongation/Stretch At Break (MD)

%

 

102

157 

98 

153

Moisture Content

Max %

8

4.3 

4.1

4.4

4.5

Ash

Max 5

1

0.78

0.71

0.50

0.54

Conductivity of Aqueous Extract

mS/m

10 Max

2.6

2.1

2.9

3.5

pH of Aqueous Extract

 

6-8

7.2

7.1

7.0 

7.4

Break Down Voltage In Air In Oil

KV/mm KV/mm

80% Stretched ( 10 layers)

10
22

10
23 

11
24

10
26

Oil Absorption

%

 

51 

52

24

26

Density

gm/cc

 

0.38

0.42

0.43

0.45

 

 

Heat Resistant Electrical Insulating Double Sided Paper Crepe Insulation Crepe Paper for Transformer

Heat Resistant Electrical Insulating Double Sided Paper Crepe Insulation Crepe Paper for Transformer

Heat Resistant Electrical Insulating Double Sided Paper Crepe Insulation Crepe Paper for Transformer

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier